4-20 mA Scaling Calculator

Scale a 4-20 mA loop signal to engineering units.

Runs in your browser. Nothing is uploaded — your input is processed on this device and discarded when you close the tab.

4-20 mA Scaling Calculator

How to use this tool

  1. Enter the loop current (or engineering value for reverse mode) and the engineering range it maps to.
  2. Press Generate. The tool scales linearly between 4 mA at the minimum and 20 mA at the maximum.
  3. Use Load sample for 12 mA over 0 to 100, or Clear to start again.

Worked example

For 12 mA over an engineering range of 0 to 100, the value is 0 + (12 - 4) / (20 - 4) x (100 - 0) = 50. In reverse, an engineering value of 50 over the same range gives 4 + (50 - 0) / (100 - 0) x 16 = 12 mA.

What this tool does not do / Limits

This assumes a perfectly linear 4-20 mA loop with 4 mA at the range minimum and 20 mA at the maximum. Real loops have calibration error, noise and fault currents below 4 mA or above 20 mA, which this tool does not model.

Frequently asked questions

Why does 4 mA mean the minimum, not zero current?

A live zero lets the system tell a real minimum reading apart from a broken wire (0 mA). That fault detection is the main reason the 4-20 mA standard exists.

What happens outside 4-20 mA?

The formula still extrapolates, but a real transmitter reading below about 3.8 mA or above about 20.5 mA usually signals a fault, not a real value — check the instrument before trusting it.